Best answer


For reference, the National Electrical Code (NEC) notes the following ampacity for copper wire at 30 Celsius: 14 AWG – maximum of20 Amps in free air, maximum of 15 Amps as part of a 3 conductor cable; 12 AWG – maximum of 25 Amps in free air, maximum of 20 Amps as part of a 3 conductor cable; 10 AWG – maximum of 40 Amps in free air, maximum of 30 Amps as part of a 3 conductor cable.

People also ask


  • What is the maximum overcurrent protection for a 14 AWG wire?

  • 240.4 (D) says unless specifically permitted in 240.4 (E) or 240.4 (G) the overcurrent protection shall not exceed 15 amps for 14 AWG. 240.4 (G) gives us specific conductor applications that permit larger overcurrent devices for small conductors.

  • What is the maximum current a 16 gauge wire can produce?

  • Or maybe the limiting parameter for your application is voltage drop, which could make the maximum current quite different again. AWG #16 copper wire has a resistance of 4.016 惟 per 1000 feet, or 4.016 m惟/foot, or 13.18 m惟/m. If you need to keep the voltage drop along 1 m of wire to 100 mV or less, then you can’t push more than 7.59 A thru it.

  • What is the voltage drop from AWG 16 to AWG 22?

  • This table says 3.7 A. According to the same table AWG 16 has a resistance of 13.17 惟 per km, which means that at 3.7 A one meter of wire would cause a power loss of 180 mW, and a voltage drop of 48 mV. PetPaulsen ‘s nomograph doesn’t show a value for AWG 16, but you can compare the values for AWG 22 with those of the table.